FOR DOWNLOADING .pdf FILE PLEASE CLICK HERE.
(The .pdf file is password protected, write your email in comment box to get password.)
1) What are the common types of generator faults?
The common types of faults occurring in synchronous generators
are:
Stator winding faults (phase to phase faults, phase to earth
faults, inter turn faults), Rotor winding faults (conductor to earth faults,
open circuit faults, inter turn faults), failure of prime mover, failure of the
field, unbalanced loading, over loading, over-voltage at generator terminals,
over-speed, ventilation failure, loss of excitation.
2) For what type of faults
does differential protection is provided?
Differential
protection responds to the phasor difference between two or more electrical
quantities. It operates for the internal faults occur in generators or
transformers. For external faults differential protection does not operate.
3) What is the disadvantage of ordinary differential protection?
When differential relaying is used for
protection, the CTs at both sides of the generator winding must be of equal
accuracy. Otherwise if the CT errors are excessive it will cause the mal
operation of the relay. To safeguard against such disadvantages percentage
differential protection is employed.
4) What is advantage of using percentage differential relay
protection?
·
It does not require CTs with air gaps
or special balancing features
·
It permits a low fault setting to be
used and this ensures maximum protection of the windings
·
It ensures complete stability under the
most severe through fault conditions
5) Explain Differential Protection?
Differential protection is generally
provided for the equipment or group of equipments which are to be protected
against internal faults. They are the primary protection systems (operates
faster) for any internal faults occurring within the protection zone.
Under healthy conditions the currents
at both ends of the windings will be equal. EMFs induced in the secondary of the
CTs will be equal and so no current flows through the operating coil of the
relay. When an earth fault or phase to phase fault occurs the condition no
longer holds good and the differential current flows through the relay
operating coils makes the relay to operate. Relay operates for the faults
occurring within the zone of protection.
6) Why Over Current Protection is not necessary for modern
generators?
Over Current protection is not
considered necessary for modern alternators because these are capable of withstanding
a complete short circuit at their terminals for sufficient time without much
over heating and damage.
7) What type of protection is provided for the generators against
overheating of the generator stator?
Resistance temperature detector is
provided.
8) Which type of relays is used for the Merz-Price protection system
for alternator?
Merz-Price protection is
differential protection provided for the alternator. The relays used in the
Merz-Price protection system of alternator are instantaneous electro-magnetic
type protection.
9) Why large alternator is grounded with large resistance?
Large capacity of alternators
are typically provided with resistance grounding. High value of resistor is
connected to the neural path to the ground. If the generator is delta
connected, then it is grounded with the help of zig-zag transformer or
(Delta-Star) transformer such that a high resistor is connected between the
neutral point and the ground. Resistance grounding is provided so as to limit
the short circuit current flowing during earth fault to stator winding in order
to provide protection against mechanical stresses and melting of winding during
Line to Ground short circuit. In large generators fault current is limited as
low as 10 to 15 amperes during short circuit.
10) Why it is not necessary to provide protection for turn to turn
fault in alternator?
The coils of the modern alternators are
single turn and therefore it is not necessary to provide protection for turn to
turn faults.
11) Why it is necessary to suppress field immediately after
disconnection of faulty alternator from the system?
In the event of fault on the
generator windings even though the generator circuit breaker is tripped, the
fault is continuous to fed as long as the excitation will exist because the emf
is induced in the generator. Hence it is necessary to suppress the field
immediately after disconnecting the faulty generator from the system.
12) Why it not necessary to provide over-voltage protection in
turbo-alternator?
The over voltage occurs when the prime mover speed increases due
to sudden loss of the load on the generator and the speed control governors in
case of turbo-generators are very sensitive to the speed variations and
therefore generator over voltage of significant duration or magnitude does not
generally occur. This is the reason why generators are not provided with over
voltage protection
13) What does the multimeter in volt meter mode show? Is it the RMS
or peak voltage?
If the multimeter is
in voltmeter mode and when it connects to AC circuits it shows the RMS value of the voltage or current. When it
connects to varying DC signals it will show RMS value only.
14) What is the PMSM?
In medium and small
size synchronous motors, DC field can be produced by permanent magnets. Such
kind of motors are called as PMSM.
15) What are the advantages and disadvantages of PMSM.
Advantages
·
Elimination of field copper loss
·
Higher power density
·
Lower rotor inertia
·
Robust construction
Disadvantages
·
Power rating low
·
Motor power factor cannot be controlled
because of field excitation cannot be controlled.
No comments:
Post a Comment